top of page

Italy, KEA inspection for Sterilizers, 4 Types and 10 Equipment

최종 수정일: 2분 전


이탈리아 베니스, 4종 10기, 멸균기 검사 보고서가 들어온다.

검사원 지적사항 및 검사 내용이 공유된다.(아래는 지적사항/ 권고 내용이다.)


Exhibit No.11 – Material Receiving/Picking Reports:Add a thickness verification field to the form and include a note at the bottom specifying tolerance information for thickness and dimension (ref. UG-16).


ree

(4종 10기, 압력부품이 자재별로 구분 정리되어 검사 대기 중..)


Rectangular Shape:The height of the rectangular part was noticeably deformed. Steel support should be used to maintain the shape (ref. UG-80).


Drawing Revision:The following points need to be confirmed:

  • Missing dimensions of body and jacket (Width × Length × Height) on main drawing

  • Missing door joint (clamp) detail

  • Missing welding detail

  • Missing PT information on design data

  • Missing required capacity of safety valve on nameplate

  • Missing hydro test information on nameplate


구조검사는 12월 초 진행 예정이다.